hwmon: (pmbus_core) Check adapter PEC support
Currently, for Packet Error Checking (PEC) only the controller is checked for support. This causes problems on the cisco-8000 platform where a SMBUS transaction errors are observed. This is because PEC has to be enabled only if both controller and adapter support it. Added code to check PEC capability for adapter and enable it only if both controller and adapter supports PEC. Signed-off-by: Madhava Reddy Siddareddygari <msiddare@cisco.com> [Upstream from SONiC https://github.com/Azure/sonic-linux-kernel/pull/215] Signed-off-by: Paul Menzel <pmenzel@molgen.mpg.de> Link: https://lore.kernel.org/r/20210605052700.541455-1-pmenzel@molgen.mpg.de [groeck: Dropped unnecessary continuation line] Signed-off-by: Guenter Roeck <linux@roeck-us.net>
Diffstat (limited to 'drivers/hwmon/pmbus')
-rw-r--r--drivers/hwmon/pmbus/pmbus_core.c9
1 files changed, 6 insertions, 3 deletions
diff --git a/drivers/hwmon/pmbus/pmbus_core.c b/drivers/hwmon/pmbus/pmbus_core.c
index 1f7fa5337974..01a1ffc74bb6 100644
--- a/drivers/hwmon/pmbus/pmbus_core.c
+++ b/drivers/hwmon/pmbus/pmbus_core.c
@@ -2216,11 +2216,14 @@ static int pmbus_init_common(struct i2c_client *client, struct pmbus_data *data,
data->has_status_word = true;
}
- /* Enable PEC if the controller supports it */
+ /* Enable PEC if the controller and bus supports it */
if (!(data->flags & PMBUS_NO_CAPABILITY)) {
ret = i2c_smbus_read_byte_data(client, PMBUS_CAPABILITY);
- if (ret >= 0 && (ret & PB_CAPABILITY_ERROR_CHECK))
- client->flags |= I2C_CLIENT_PEC;
+ if (ret >= 0 && (ret & PB_CAPABILITY_ERROR_CHECK)) {
+ if (i2c_check_functionality(client->adapter, I2C_FUNC_SMBUS_PEC)) {
+ client->flags |= I2C_CLIENT_PEC;
+ }
+ }
}
/*